16   PtAngSpBl1: pitch angle setpoint is using MV

This tissue has following status: green

Created: 14 Mar 2010

Links:

Page: 19

Clause: 6.2.2

Paragraph: Table 8

Category: Issue for edition 2 of this part

Issue: WROT defines PtAngSpBl1 as pitch angle setpoint and PtAngValBl1 as pitch angle value. MV cdc is usually used only for measured values.

If PtAngSpBl1 is a setpoint it should be analyzed if APC common data class could be used.

Proposal: PtAngSpBl1 (MV) and PtAngValBl1 (MV) could be reduced to only one data of the class SPV. This cdc includes the setpoint and the current measured value.

PtAngSpBl1.actVal.ctlVal.f <-- setpoint value
PtAngSpBl1.actSt.mxVal.f <-- measured value



 