Issue: There is no concept for other wind farm components i.e. power management or meteorological units
- WTUR (wind turbine …) with
- TotWh (total active energy production) as mandatory attribute TurSt (turbine status)
- W (active power generation)
- SetTurOp (wind turbine …)
- WROT (wind turbine rotor…)
- WGEN (wind turbine generator…)
- WYAW (wind turbine yawing…)

A meteorological unit has no rotor, generator or yawing mechanism

Proposal: Change the LNs WROT, WGEN, WNAC and WYAW from mandatory to optional.

 